Solar DCDB
Every inverter and charge controller, whether in a utility-interactive or stand-alone system, has a DC input voltage window that must be adhered to. In batteryless grid-tied systems, inverters require relatively high DC input voltages, from 90 to 850V (typically 4 to 26 modules wired in series).
Small grid-tied PV systems (less than 5 kW @ 600V DC) often have only one or two series strings of modules. GEESYS Team will configure the SJB based on the Inverter’s technical specification and Solar PV modules technical specification. A combiner box offers a place to house series fuses and parallel the series string inputs, reducing the number of array output wires needed to run to the inverter location.
Some grid-direct inverter manufacturers include series fusing within the inverter or its attached disconnect box, which may eliminate the need for a separate combiner box. However, using a PV combiner box located close to the PV array gives you easy access to the wires for each series string. This can be handy for troubleshooting a malfunctioning PV array without having to run back and forth to the inverter area.
Configuration
- SJB 1in – 1out
- SJB 2in – 2out
- SJB 3in – 3out
- SJB 4in – 4out
- SJB 4in – 2out
- SJB 6in – 2out
- SJB 6in – 4out
- SJB 6in – 6out
- SJB 8in – 4out
- SJB 8in – 8out
- SJB 10in – 10out
- SJB 12in – 12out
Solar String combiner Boxes
|
| Model |
GPRO-GD5X |
GPRO-GD10X |
| Maximum Voltage in open Circuit |
500V |
1000V |
Input
| Maximum Input Fuse* Rating, A * |
6/10/12/15/20/30 |
| Max Input Current in short Circuit |
|
| Max. input current in short circuit at STC |
|
| Maximum string current per fuse holder with all string fuse* |
Reduction factor 0.55 |
| Conductor Size , Sq.mm |
4 — 10 Sq.mm |
Output
| No of DC Outputs 1 - 12 |
150 Sq. |
| Maximum DC Current, A * |
Upto 32A |
Upto 32A |
| Conductor Size, Sq.mm |
4 — 10 Sq.mm |
4 — 10 Sq.mm |
| Cable gland clamping range,mm |
12-32 |
|
Protection
| DC inputs overcurrent protection |
Protection on both polarities, gPV fuses, size 10 x 38 mm, max. rating 30 A (fuses not provided with product) |
| Surge Protection Device (SPD)* |
<=600V DC, Class C/Class B/ Class B+C
|
1000V DC, Class C/Class B/ Class B+C |
| Electric shock protection |
Class II equipment |
General
| Ingress Protection |
IP66/65 |
| Enclosure Type |
PS*/PC, |
| Transparent |
Top Cover |
| Wall mounting |
Yes |
| Bus Bar* |
Yes |
| Operating conditions Temp : |
-20 to +55 Deg. C , RH : 0 — 95% non cond |
| Type of Protections |
Short-Circuit,Surge |
| International standards followed |
IEC 60364 |
| Design Life |
25 years + |